ACS580-01-106A-4
Product Overview
-
Model: ABB ACS580-01-106A-4
-
Type: Wall-mounted general-purpose VFD (ACS580-01 series)
-
Power Ratings:
-
Normal Duty (Pn): 55 kW — 106 A (AC-3)
-
Light Overload (PLd): 55 kW — 100 A
-
Heavy Duty (PHd): 45 kW — 87 A
-
-
Input Voltage: 380–480 V AC, 3-phase
-
Frame / Enclosure: R5 / IP21 standard (IP55 optional)
-
Efficiency Class: IE2 — Standby Power Loss: ~24 W
Physical Specifications
-
Dimensions (W × H × D): 203 × 732 × 295 mm
-
Net Weight: ~28.3 kg
Performance & Functional Features
-
Overload Capacity:
-
150% for 60 seconds every 10 minutes (heavy-duty overload)
-
110% for 60 seconds for fan/pump operation (light overload)
-
-
Control Modes: V/f and Sensorless Vector (full closed-loop available via encoder)
-
Safety & EMC: Safe Torque Off (STO) and integrated C2-grade EMC filter standard
-
Setup Tools & Connectivity:
-
Assistant control panel
-
USB interface
-
RS-485 with Modbus RTU/IP
-
Fieldbus support: Modbus, PROFIBUS, PROFINET, EtherNet/IP, DeviceNet
-
I/O: 2 analog inputs, 2 analog outputs, 6 digital inputs, 3 relay outputs
-
Summary Table
| Feature | Specification |
|---|---|
| Power (Nominal / Light / HD) | 55 kW / 55 kW / 45 kW |
| Current (Normal / Light / HD) | 106 A / 100 A / 87 A |
| Voltage Supply | 380–480 V AC, 3-phase |
| Frame / Enclosure | R5 / IP21 (IP55 optional) |
| Dimensions (W×H×D) | 203 × 732 × 295 mm |
| Net Weight | ~28.3 kg |
| Efficiency / Standby Loss | IE2 / ~24 W |
| Overload Ratings | 150% high; 110% fan/pump |
| Control Modes | V/f and Sensorless Vector |
| Safety & EMC | STO; C2 EMC filter |
| Setup Tools | Assistant panel, USB, DriveWindow Light |
| Connectivity & I/O | RS-485, fieldbus support, AI, AO, DI, RO |
Couldn't load pickup availability
- Express Delivery
- 12 Months Warranty
- 7 Days Easy Replace
-
Vendor:
ABB