ACS580-01-05A7-4
Product Overview
-
Model: ABB ACS580-01-05A7-4
-
Type: Wall-mounted general-purpose VFD (ACS580-01 series)
-
Normal Duty Output (Pn): 2.2 kW — 5.6 A (AC-3)
-
Light-Overload Rating (PLd): 2.2 kW — 5.3 A
-
Heavy-Duty Rating (PHd): 1.5 kW — 4.0 A
-
Input Voltage: 380–480 V AC, 3-phase
-
Frame / Enclosure: R1 / IP21 (indoor, wall-mount)
-
Efficiency Class: IE2 — Standby Loss: ~14 W
Mechanical Specifications
-
Dimensions (W × H × D): 125 mm × 373 mm × 223 mm
-
Net Weight: ~4.6 kg
Performance & Features
-
Overload Capacity:
-
150 % for 60 s every 10 min (High Overload)
-
110 % for 60 s in fan/pump applications
-
-
Speed Range: 0–500 Hz
-
Control Modes: V/f and Sensorless Vector
-
Safety & EMC: Safe Torque Off (STO); integrated C2-grade EMC filter
-
Setup Tools:
-
Assistant control panel
-
FlashDrop (offline parameter copy)
-
DriveWindow Light (PC-based setup)
-
-
Connectivity & I/O:
-
2 analog inputs, 2 analog outputs
-
6 digital inputs, 3 relay outputs
-
USB and RS-485 for Modbus RTU communications
-
Fieldbus-ready (Modbus, PROFIBUS, EtherNet/IP, DeviceNet, etc.)
-
Summary Table
| Feature | Specification |
|---|---|
| Power (Pn / PLd / PHd) | 2.2 kW / 2.2 kW / 1.5 kW |
| Current (Normal / Overload / HD) | 5.6 A / 5.3 A / 4.0 A |
| Voltage Supply | 380–480 V AC, 3-phase |
| Frame / Enclosure | R1 / IP21 |
| Dimensions (W×H×D) | 125 × 373 × 223 mm |
| Net Weight | ~4.6 kg |
| Efficiency / Standby Loss | IE2 / ~14 W |
| Speed Range | 0–500 Hz |
| Control Modes | V/f & Sensorless Vector |
| Safety & EMC | STO, C2 EMC filter |
| Setup Tools | Assistant panel, FlashDrop, DriveWindow Light |
| I/O & Connectivity | Analog + digital I/O, USB, fieldbus interfaces |